MAGNETIC CIRCUIT (CORE) :
Cold rolled grain oriented steel sheets with higher magnetic current carriage capacity having a thickness of M5 0.30 mm are used in our cores, which are manufactured in the form of type E with the appropriate methods; and iron losses in our products and voice level is kept low by this way.

TANK :
Our transformer tanks, on which imperviousness and endurance tests have been executed in accordance with TS 267 product standard, are manufactured in two types: with radiator or with corrugated wall. Our products, on which Temperature Increase Tests have been executed, are equipped with radiators/corrugated walls of appropriate size and quantity to provide sufficient cooling.

Click on the picture to enlarge.


WINDING :
I-Primary Windings:
Layer spaces of our high voltage windings, which are winded with round enamelled covered copper bobbin wires for lower currents and with flat copper conductors with paper isolation for higher currents, are isolated using insulating materials having various thickness and types, manufactured from pure cellulose.

II-Secondary Windings:
These are winded by using flat copper conductors with paper isolation. .

Click on the picture to enlarge.


INSTALLATION :
Our windings are combined together with cores by our trained operators under control of experienced engineers and these are coupled in accordance with the connection group. After all the required tests are executed on the transformer, drying process is executed in isolation drying furnaces. Transformers are filled with isolation oil of high quality, which a separation process (regain humidity) under -1 Atm environment in vacuum chamber is executed, after isolation drying process.

Click on the picture to enlarge.


PAINT :
After the sides of tank, which are cleaned using chemical methods, are lined with epoxy material, they are painted with RAL 7033 coloured final layer industrial paint in order not to experience the negativity like rust and corrosion, which may originate from the conditions of the facility, on our manufactures.

Click on the picture to enlarge.


TESTS EXECUTED ON OUR TRANSFORMERS :

Quality means the appropriateness to the pre-planned conditions. Therefore, all ELKIMA branded products are controlled by experienced engineers and technicians in order to provide the required criteria.



All the ELKIMA branded transformers are manufactured in accordance with all requirements of TS 267 EN 60076 product standards. Therefore, our products are subjected to all routine tests required by related standards; and also typical and specific tests are performed in accordance with customer demands.All tests are performed with computer support.


Routine Tests
a- Measurement of winding resistance
b- Measurement of voltage turning ratio and control of phase sliding.
c- Measurement of short-circuit impedance and loss in load.
d- Measurement of no-load loss and current
e- Seperate-source withstand test
f- Induced overvoltage withstand test
g-Measurement of insulation resistance
(Tests will be applied to all manufactured transformers.)
Type tests
a- Temperature rise test
b-Measurement of transformer sound level
c- Full wave impulse voltage test
d- Non-leakage test
e- Measurement of paint thickness
( Tests will be applied to one product representing the whole party.)
Specific tests
a- Dielectric specific tests
b- Measurement of the capacities of windings within themselves and against ground.
c- Measurement of zero-sequence impedance in three phased transformers.
d- Demonstration of the ability to withstand the dynamic effects of short circuit. (It is applied
abroad)
e- Measurement of no-load current harmonics.
f- Measurement of windings' insulation resistance against ground and measurement of loss factor of
insulation system capacity.
( Except 3-a, tests will be applied in our factory in consideration of payment. Short circuit resistance test can be applied in an independent laboratory. These certificates are extant for our prior manufactures.)
Transformer oil tests
a- Measurement of dielectric strenght.
b- Nomination of colour count
c- Measurement of water quantity
d- Measurement of neutralisation value ( acid quantity)
e- Measurement of interfacial tension
f-Measurement of power factor
( Tests will be applied to a sample taken from a transformer representing the whole party.)

POINTS TO BE MENTIONED IN REQUEST FOR OFFER
· Transformer quantity
· Rated power (kVA)
· High voltage and Low voltage nominal values. (kV)
· Number of temperature.
· Connection group.
· Equipment demanded to be added.
· Place of operation (environmental heat, counter line)
· Parallel operating situation, if exists state information of  the transformers that it will operate parallel with.
· Standard to be applied / Specification (Contract)
· Specific terms if exist.

STANDARD ACCESSORIES
· Marking plate
· Off-load top changer
· Oil filling plug
· Oil dirain and sampling valve.
· Oil level indicator
· Two grounding terminals. One on tank and the other one on the cover.
· Thermometer pocket.
· Air breather connection flange.
· Arcing horns (eclator rods)

EQUIPMENT TO BE ADDED ON REQUEST
· Buchholz relay
· Thermometer with alcohol
· Dial Thermometer with double contacts.
· Air breather
· Wheels that can be adjusted in two axis.
· Terminal box.